A guide for Gas Safe registered engineers.

Gas tightness test procedure

Under IGEM/UP/1B Edition 4, a natural gas tightness test has three stages: a let-by test at 7 to 10 mbar for 1 minute, 1 minute of stabilisation at the test pressure of 20 mbar, then a further 2-minute test. The permissible drop now depends on installation volume, not meter type, and pipework-only tests must show no perceptible movement.

Last updated

Which edition applies now

The procedure for small installations is set by IGEM/UP/1B. Edition 4 was published in March 2026. Edition 3 was withdrawn on 30 September 2026, so every tightness test from 1 October 2026 follows Edition 4.

The stages and timings did not change. What changed is how you judge a pressure drop: the limit now depends on the installation volume (IV), not on the meter type. If you learned the drop figures by meter (E6, U6, U16), those tables belong to the withdrawn edition.

This page is a summary for registered engineers, not the standard. Follow the current IGEM/UP/1B and the manufacturer’s instructions for your gauge. You remain responsible for the test and the result. ClearWorks is not affiliated with IGEM or Gas Safe Register.

When a tightness test is required

Regulation 6(6) of the Gas Safety (Installation and Use) Regulations 1998 requires anyone whose work on a gas fitting might affect gas tightness to test the installation immediately afterwards, at least as far as the nearest valves upstream and downstream.

IGEM lists the circumstances in which IGEM/UP/1B Edition 4 applies to tightness testing:

  • new installations and new extensions to existing pipework
  • alteration, replacement, re-use or upgrading of an existing installation
  • before and after any work on an existing installation that may affect gas tightness
  • a known or suspected gas escape
  • a complete loss of supply or installation pressure
  • routine testing of existing installations, and immediately before purging

Scope of IGEM/UP/1B Edition 4

IGEM gives the scope as installations with pipework up to 35 mm nominal bore, a meter with a badged capacity up to 16 m³/h, and an installation volume up to 0.035 m³ in an individual dwelling or non-domestic premises. For natural gas the operating pressure at the meter outlet is up to 21 mbar. Anything larger is outside this standard. For volumes over 0.035 m³, IGEM points to IGE/UP/1.

The three stages: let-by, stabilisation, test

  1. Let-by test. This proves the emergency control valve shuts off fully. With the valve closed and the gauge reading 7 to 10 mbar, watch it for 1 minute. A rise means the valve is passing gas. Deal with that first, because a tightness test cannot be trusted while the valve is passing.
  2. Stabilisation. Raise the pressure to the tightness test pressure for the fuel gas, isolate, and leave it for 1 minute so the pressure and temperature settle. Adjust back to test pressure if needed.
  3. Test. Watch the gauge for a further 2 minutes.

Registered Gas Engineer, Gas Safe Register’s magazine, gives the natural gas test pressure as 20 mbar. If that cannot be reached, Edition 4 allows a test at no less than 18 mbar, with operating pressure checks to IGEM/G/13 after a pass. If even 18 mbar cannot be reached, isolate the installation and find out why the pressure is low before you test.

Natural gas tightness test at a glance (IGEM/UP/1B Edition 4, as summarised in Industry Standard Update 133 Edition 2)
Stage or caseFigure
Let-by test7 to 10 mbar for 1 minute
Stabilisation1 minute at test pressure
Test periodA further 2 minutes
Pipework only, or only new appliances connectedNo perceptible movement
Existing appliances, IV up to 5 litres (0.005 m³)Up to 8 mbar
Existing appliances, IV over 5 and up to 10 litresUp to 4 mbar
Existing appliances, IV over 10 and up to 15 litresUp to 2.5 mbar
Existing appliances, IV over 15 and up to 35 litresUp to 1 mbar

Natural gas only. LPG and LPG/air have their own limits in the standard. A drop inside the limit is not a pass on its own: see Maximum permissible pressure drop.

On-site checklist

The same steps as this page, in order, for natural gas under IGEM/UP/1B Edition 4. Print it or keep it open on your phone.

Before you start

  1. Check the installation is in scope: pipework up to 35 mm, meter up to 16 m³/h, installation volume up to 0.035 m³, natural gas at up to 21 mbar.
  2. Set the appliances up for the test, for example cooker lids up and permanent pilots out. Zero the gauge (water or electronic) and use it as its manufacturer instructs.
  3. If you can smell gas, it is not a pass, whatever the gauge reads.

Test

  1. Let-by: emergency control valve closed, gauge at 7 to 10 mbar, watch for 1 minute. Any rise: the valve is passing. Deal with it before going on.
  2. Stabilise: raise to test pressure (20 mbar for natural gas; if 20 mbar cannot be reached, no less than 18 mbar, with operating pressure checks to IGEM/G/13 after a pass), isolate, wait 1 minute. Adjust back to test pressure if needed.
  3. Test: watch the gauge for a further 2 minutes. Note the drop.

Judge the result

  1. Pipework only, or only new appliances: no perceptible movement (no more than 0.25 mbar on a water or electronic gauge, no more than 0.2 mbar on an electronic gauge reading to one decimal place).
  2. Existing appliances and no smell of gas: if the gauge moved, work out the installation volume, compare the drop with the limit in the table above, then isolate the appliances and retest the pipework. The pipework test must show no perceptible movement. If an appliance cannot be isolated, leave it connected and apply the same no-movement rule.
  3. Fail: trace and repair the escape. If you cannot repair it, disconnect and make safe. Where you leave something unsafe, follow the Gas Industry Unsafe Situations Procedure (IGEM/G/11) and issue a warning notice.

Finish and record

  1. Remove the gauge, refit the test nipple, reconnect any isolated appliances and turn the gas on.
  2. Check every disturbed joint with leak detection fluid, and any pipework between an isolation valve and the appliance it serves.
  3. Record the result, the drop you measured and the edition you tested to.

A summary of the steps on this page, not the standard. Work to the current IGEM/UP/1B and the manufacturer’s instructions. You remain responsible for the test.

Maximum permissible pressure drop

New installations and pipework-only tests

There is no allowance. Where you test pipework on its own, or with only new appliances connected, the gauge must show no perceptible movement.

Existing installations with appliances connected

A drop can be acceptable only where existing appliances are connected and there is no smell of gas. Under Edition 4 the steps are:

  1. If the gauge moves, work out the installation volume: the meter plus the pipework, from its lengths and diameters.
  2. Compare the drop with the limit for that volume. The smallest installations are allowed the most, and the largest in scope are allowed 1 mbar, so a drop of 1 mbar or less is inside the limit whatever the volume.
  3. Even inside the limit, you must show the drop is not coming from the pipework. Isolate the appliances and repeat the test on pipework only. This time there must be no perceptible movement. If an appliance cannot be isolated, test with it connected and apply the same no-movement rule.

Where pipework is hidden, Registered Gas Engineer’s guidance is to estimate the run and assume the largest visible pipe size continues until the pipe reappears. That overstates the volume, so the limit you work to errs on the safe side.

By meter type

Edition 4 has no drop table by meter type. The meter still matters, because its volume is part of the installation volume, but the limit is read from the volume. The Edition 3 meter figures no longer apply.

The gauge: what counts as movement

A gas pressure tester for this job is a manometer, either a water U-gauge or an electronic gauge. “No perceptible movement” is defined by the gauge type:

  • Water gauge: a movement of 0.25 mbar or less is treated as not perceptible.
  • Electronic gauge: a maximum of 0.25 mbar.
  • Electronic gauge reading to one decimal place: a maximum of 0.2 mbar.

Use the gauge as its manufacturer instructs, including zeroing and calibration.

If the test fails

If the drop is outside the limit, or the pipework-only test shows movement, trace and repair the escape. If you cannot repair it, disconnect the installation from the gas supply and make it safe. A smell of gas is never a pass, whatever the gauge reads.

Edition 3 is withdrawn, so its meter-based figures cannot be used to pass an installation that fails under Edition 4. Where you leave something unsafe, follow the Gas Industry Unsafe Situations Procedure (IGEM/G/11) and issue a gas warning notice.

After a pass: remove the gauge, refit the test nipple, reconnect any appliances you isolated, turn the gas on, and check every disturbed joint with leak detection fluid. Where appliances were isolated, also check the pipework between each isolation valve and its appliance.

Recording the result

Write down what you measured: pass or fail, and any drop. Gas Safe Register recommends noting on your work records which edition of the procedure you used.

The result goes on the record for the job, such as the landlord gas safety record (CP12) or the gas service record.

In ClearWorks the result goes straight onto the record you are filling in, and missing details are flagged before you sign. You still carry out and judge the test.

See the gas certificate app

Common mistakes

  • Skipping let-by. A passing valve can hide a leak by topping the pressure up.
  • Using the old meter table. From 1 October 2026 the limit comes from the installation volume.
  • Stopping at “within limits”. The pipework-only retest is part of the test.
  • Timing the test from the wrong point. The 2 minutes start after the 1 minute of stabilisation.
  • Blaming the weather. Movement has to be investigated, not put down to temperature or the meter.
  • Forgetting the joints you disturbed. Use leak detection fluid on the test nipple and every joint you touched.

Sources: IGEM, IGEM/UP/1B Edition 4 (scope, when the standard applies, IGE/UP/1 for larger volumes, publication and withdrawal dates). Registered Gas Engineer, Industry Standard Update 133 Edition 2 (appliance set-up, stages, timings, drop limits by installation volume, gauge movement, appliances that cannot be isolated). Registered Gas Engineer, “Updated tightness testing standard: what you need to know”, 11 May 2026 (test pressure, pipework-only retest, leak detection fluid checks, IGEM/G/11, hidden pipework, recording the edition). Logic4training, IGEM/UP/1B Edition 4 (investigating movement). Gas Safety (Installation and Use) Regulations 1998, regulation 6(6). Last checked 18 November 2026.

Gas tightness test questions

How long does a gas tightness test take?

For natural gas under IGEM/UP/1B Edition 4: a let-by test of 1 minute, then 1 minute of stabilisation at test pressure, then a test period of a further 2 minutes.

What is a let-by test?

It checks that the emergency control valve shuts off fully. With the valve closed, the gauge is held at 7 to 10 mbar for 1 minute. A rise means the valve is passing gas.

What pressure drop is allowed on a gas tightness test?

None on new pipework, pipework-only tests or where only new appliances are connected. With existing appliances and no smell of gas, the natural gas limit runs from 8 mbar on the smallest installations down to 1 mbar, depending on installation volume, and the pipework itself must still show no perceptible movement.

Is the permissible drop still based on the meter type?

No. IGEM/UP/1B Edition 3 was withdrawn on 30 September 2026. Edition 4 sets the limit by installation volume, which includes the meter and the pipework.

What gas pressure tester do I need?

A manometer, either a water gauge or an electronic gauge. Edition 4 treats movement of up to 0.25 mbar as not perceptible, or 0.2 mbar on an electronic gauge that reads to one decimal place.