For Gas Safe engineers · By ClearWorks · Last updated 25 November 2026
How to fill in a CP12 gas safety certificate
To fill in a CP12 landlord gas safety record, inspect every landlord-provided appliance and flue under regulation 26(9) of GSIUR 1998, then record all nine legal items under regulation 36(3)(c). Issue the completed record on the day, even if defects need follow-up work.
Is there one official CP12 layout engineers must use?
No. HSE guidance on gas safety check records confirms that Gas Safe Register does not produce its own CP12 form and the law does not dictate a layout. What matters legally is that every field required by regulation 36(3)(c) of the Gas Safety (Installation and Use) Regulations 1998 is present and accurate.
Gas Safe Register FAQs also confirm that the record does not have to carry the Gas Safe Register logo, whether you use a printed pad, a bespoke sheet or a CP12 app.
What nine items must be on every CP12 record?
Regulation 36(3)(c) sets out the exact nine statutory items. Missing any one of them leaves the landlord with an incomplete record.
| Sub-clause | Required field | What to write on site |
|---|---|---|
| 36(3)(c)(i) | Date of check | Actual date the appliance or flue was inspected |
| 36(3)(c)(ii) | Property address | Full address where the appliances and flues are installed |
| 36(3)(c)(iii) | Landlord or agent details | Name and address of the landlord, or their managing agent |
| 36(3)(c)(iv) | Appliance and flue description | Location, appliance type and flue arrangement for every item checked |
| 36(3)(c)(v) | Safety defects identified | Clear description of any safety defect found, or none if clear |
| 36(3)(c)(vi) | Remedial action taken | Action taken on site, including isolation or warning notice issued |
| 36(3)(c)(vii) | Regulation 26(9) confirmation | Confirmation the safety check covered every matter in regulation 26(9) |
| 36(3)(c)(viii) | Engineer identity | Name and signature (written or electronic) of the engineer who did the check |
| 36(3)(c)(ix) | Registration number | Gas Safe registration number of the engineer or their employer |
If you still check fields manually on paper, our printable CP12 template lists all nine mandatory items beside useful optional fields such as make, model, serial number and combustion readings.
What physical checks must you complete before ticking regulation 26(9)?
Before you confirm compliance with regulation 26(9) of GSIUR 1998, the inspection of each landlord-provided appliance and flue must examine:
- The effectiveness of the flue: visual integrity, termination clearances, seals and flue flow or spillage tests where applicable.
- The supply of combustion air: permanent ventilation sizing and unobstructed air paths where required by the appliance and standards.
- Operating pressure or heat input, or both: checked where necessary, or combustion performance analysis where examining pressure or heat input is not reasonably practicable.
- Safe operation: flame picture, safety shut-off devices, controls, and tightness of the gas installation.
Use our gas rate calculator on site when clocking a meter to convert metric or imperial readings into gross and net kW.
Note that HSE landlord FAQs warn engineers and landlords not to assume a boiler service automatically covers every point in a gas safety check, or vice versa. If you carry out both on the same visit, record the gas service record separately or clearly alongside the safety check.
How should you record defects and unsafe situations on a CP12?
When you find a defect or an unsafe situation, follow the Gas Industry Unsafe Situations Procedure (GIUSP) and classify it accurately as Immediately Dangerous (ID) or At Risk (AR). As noted in HSE guidance, you must still issue the landlord gas safety record upon completing the check and must not hold it back until remedial repairs are finished.
- Record the specific defect under item 36(3)(c)(v) and the immediate action taken (disconnected or switched off, warning label applied, warning notice issued) under item 36(3)(c)(vi).
- Issue a separate gas warning notice and reference it on the CP12 so the landlord has clear evidence of what was isolated and why.
- Do not use obsolete "Not to Current Standards (NCS)" labels on safety paperwork; Gas Safe Register removed NCS in 2016 so critical safety messages are not diluted.
What about tenant-owned appliances and common pitfalls?
According to HSE guidance on what needs a gas safety check, the landlord's statutory duty covers appliances and flues they own and provide for tenants, plus associated pipework even if a tenant owns the appliance. HSE recommends checking any chimney or flue serving a tenant-owned gas appliance as part of the visit, while noting clearly on the record which appliance belongs to the tenant.
Common errors that trigger rework or agent rejection include forgetting the landlord's or agent's address, omitting an open-flued fire or gas hob in the kitchen, leaving out the engineer's signature, or sending the form without your Gas Safe registration number. ClearWorks flags missing fields and out-of-range readings before you can sign, and opens the warning notice automatically if you mark an appliance unsafe.
Frequently asked questions
Can I issue a CP12 without the landlord's signature?
Yes. HSE guidance states that the landlord does not have to sign the record, although the landlord's or letting agent's name and address must be recorded on it.
Should I withhold the CP12 if a boiler fails the check?
No. HSE guidance states the gas safety check record should be issued once the checks are completed and must not be delayed until remedial work is carried out.
Are electronic signatures and emailed CP12s valid?
Yes. Both HSE and Gas Safe Register confirm electronic records and electronic signatures are acceptable, provided the record identifies the engineer, is secure from tampering and can be printed if needed.
How does ClearWorks reduce CP12 form errors on site?
ClearWorks pre-fills appliances and landlord details from the previous year's record, flags missing mandatory fields or out-of-limits readings before sign-off, and works offline. You remain responsible for the inspection and certificate.
Related pages
Sources: Gas Safety (Installation and Use) Regulations 1998, regulation 36; regulation 26(9); HSE, Gas safety check records and what to keep; HSE, Gas safety checks: what needs them?; HSE, Gas safety: landlords and letting agents FAQs; Gas Safe Register, FAQs. Last checked 25 November 2026. This article is a practical summary for engineers and electricians, not legal advice or a substitute for BS 7671, GSIUR 1998 or Gas Safe guidance. ClearWorks is not affiliated with or endorsed by Gas Safe Register, HSE, the IET, Electrical Safety First, NICEIC or NAPIT.
Issue your next CP12 on site
Your first 3 certificates are free. No card needed.
Founding London engineers keep their price for as long as they stay subscribed.