Unvented cylinder: how it works, vented vs unvented, and G3
An unvented hot water cylinder stores hot water in a sealed vessel with no vent pipe. Fed from the mains, it delivers hot water at mains pressure. This guide covers how it differs from a vented cylinder, what direct and indirect mean, the safety devices Approved Document G expects, and who may install one.
Last updated
What an unvented cylinder is
An unvented hot water cylinder is a sealed store of hot water with no vent pipe. Approved Document G, the government guidance for England, calls it an unvented (closed) hot water storage system and defines it in three parts:
- the vessel is fed with cold water from a supply pipe or a dedicated storage cistern, without a vent pipe
- the water is heated directly or indirectly
- the system has room for the water to expand as it heats, plus safety devices that stop it passing 100°C
Fed from the mains supply pipe, it delivers hot water at mains pressure, up to the limit set by the pressure reducing valve on the inlet. One manufacturer’s manual describes its range as unvented mains pressure hot water storage.
Vented vs unvented hot water cylinder
A vented cylinder is fed from a cold water storage cistern (a storage tank). HSE’s guidance lists hot and cold water storage with a gravity fed system as one of the basic system types.
| Point | Vented (open) | Unvented (closed) |
|---|---|---|
| Cold feed | A dedicated cold water storage cistern | A supply pipe, or a dedicated cistern |
| Vent pipe | Runs from the top of the cylinder to a point open to the air, above the cistern | None |
| Where expanding water goes | Back up the cold feed pipe | Into an expansion vessel or a space inside the cylinder |
| Protection against overheating | The vent pipe, plus a cut-out or a relief valve | At least two independent safety devices, on top of the thermostat |
For both types, requirement G3 of the Building Regulations says the stored water must never exceed 100°C.
Direct vs indirect unvented cylinder
Direct and indirect describe how the water is heated, not how the cylinder is fed. Approved Document G defines both:
- Direct. The heat source is part of the hot water vessel. The document’s first example is an electric immersion heater.
- Indirect. The stored water is heated through a heat exchanger. In practice that is a coil inside the cylinder.
One manufacturer sells indirect cylinders for gas or oil boilers, and a version with a coil designed for air source or ground source heat pumps. See our heat pump engineer guide. Its manual says its unvented cylinders must not be used with solid fuel boilers.
An immersion heater needs electrical work. For hot water installations in dwellings, Approved Document G draws attention to Part P.
Unvented cylinder diagram: the safety devices
- Cold supply. Cold water enters under pressure.
- Expansion vessel. Approved Document G defines it as a vessel that temporarily takes up the expansion of the water as it is heated. It also allows expansion to be taken up inside the cylinder.
- Thermostat. Controls the stored temperature. It does not count as one of the two safety devices.
- Energy cut-out. A non-self-resetting device that cuts the heat to the cylinder if it overheats. It can only be reset by hand.
- Temperature and pressure relief valve. Opens to let water out if a factory-set temperature or pressure is passed. It sits directly on the cylinder.
- Tundish. A device in the discharge pipe that gives an air break and shows when a valve is discharging. It should be in the same space as the cylinder, with no more than 600mm of pipe from the valve.
- Discharge pipe. Carries hot water and steam from the tundish to a safe place. The guidance asks for metal, or another material shown to withstand the temperature.
The cut-out plus the relief valve is the pairing Approved Document G gives as an acceptable approach. Cylinders up to 500 litres and under 45kW should come as a proprietary unit or package.
The warning label the document asks for tells users not to remove or adjust any part, and to switch the heater off and contact the installer if hot water flows from the discharge pipe.
Who can install one: G3 and building control
Fitting an unvented cylinder is work for a competent installer, not a DIY job. Approved Document G tells owners to choose installers with the necessary skills, and gives two examples of how those skills are shown: registration with a competent person scheme for this type of work, or a current registered operative skills certification card for unvented hot water systems.
Installation is also notifiable building work. There are two routes:
- Tell building control first. The building control body must be notified before work starts.
- Use a registered installer. Under regulation 12(6) and Schedule 3, an installer registered with a competent person scheme for the work self-certifies it. The occupier should get a compliance certificate within 30 days of completion.
Schedule 3 lists the work as installation of a heating or hot water system. GOV.UK keeps the current list of scheme operators for that work, and Approved Document G notes that the schemes change from time to time. Ask whether the installer’s registration covers unvented hot water.
G3 unvented course
Training for this work points back to requirement G3. One example is BPEC’s Domestic Hot Water Storage Systems (Unvented) qualification. BPEC says its England and Wales manual covers Approved Document G3, Part L1 and Part P, that there are three assessments including one practical, and that certificates are valid for 5 years. For gas work, see Gas Safe registration.
Servicing and stored temperature
Approved Document G does not set a service interval. The manufacturer’s instructions do. One manufacturer’s manual says maintenance is normally carried out at least annually and recommends a maximum of 12 months between visits, by a competent person qualified to work on unvented cylinders. Check the manual for your own cylinder.
It also tells users that water flowing through the tundish is a fault that needs a maintenance visit, and never to tamper with the safety valves. If the discharge is hot and continuous, it says to turn off the boiler or immersion heater, but not to turn off the cold water to the cylinder until the discharge is cold. It suggests timing routine maintenance with the boiler service. See also the boiler commissioning checklist.
On temperature, HSE’s legionella guidance says hot water should be stored at 60°C or more and reach 50°C at the outlets within 1 minute. Those duties fall on employers and people in control of premises, including landlords. Separately, Approved Document G limits the hot supply to a bath to 48°C in a new dwelling or one formed by a change of use.
For gas engineers and electricians
ClearWorks is a certificate app for Gas Safe registered engineers and electricians.
- Gas. Landlord gas safety record, warning notice, service record and breakdown record. See the gas certificate app.
- Electrical. EICR, EIC and minor works. See the EICR software.
- Checked as you go. Missing details and readings outside limits are flagged before you sign.
The gas plan or the electrical plan is £15 per engineer a month + VAT with unlimited certificates. Gas and electrical together is £24. Pay as you go is £2.50 a certificate + VAT. The first 3 certificates are free. See pricing.
This page is a summary for England, not a design or installation guide. The installer must follow the current Approved Document G, the Water Fittings Regulations and the cylinder manufacturer’s instructions, and remains responsible for the work. ClearWorks is not affiliated with Gas Safe Register, BPEC, HSE, or any competent person scheme or manufacturer named here.
Sources: GOV.UK, Approved Document G (2015 edition incorporating 2016 and 2024 amendments, PDF): key terms, the “Notification of work” guidance, requirement G3 and paragraphs 3.5, 3.12 to 3.13, 3.17 to 3.24, 3.38 to 3.42, 3.50 to 3.63 and 3.65; Building Regulations 2010: regulation 12 and Schedule 3; GOV.UK, current competent person schemes; BPEC, Domestic Hot Water Storage Systems (Unvented); HSE, legionella: hot and cold water systems; Gledhill, unvented cylinder instruction manual and heat pump cylinder page, used only as an example of manufacturer wording. Last checked 18 November 2026.
Unvented cylinder questions
What is an unvented cylinder?
It is a sealed hot water storage cylinder with no vent pipe. Approved Document G describes it as a vessel fed from a supply pipe or dedicated cistern, heated directly or indirectly, with space for expansion and safety devices that stop the water exceeding 100°C.
What is the difference between a vented and an unvented hot water cylinder?
A vented cylinder is fed from a cold water storage cistern and has a vent pipe open to the air above that cistern. An unvented cylinder has no vent pipe, so it relies on an expansion vessel or internal space and at least two independent safety devices.
What is the difference between a direct and an indirect unvented cylinder?
In a direct cylinder the heat source is part of the vessel, such as an electric immersion heater. In an indirect cylinder the stored water is heated through a heat exchanger, a coil fed by a boiler or a heat pump.
What does G3 mean on an unvented cylinder?
G3 is the hot water requirement in Part G of Schedule 1 to the Building Regulations 2010. Approved Document G explains how to meet it. Training bodies and manufacturers use the label too: BPEC says its unvented course covers Approved Document G3, and one manufacturer’s manual refers to Part G3 components.
Do you need to tell building control about an unvented cylinder?
Yes in England. Approved Document G says installing an unvented system is notifiable building work. Either building control is told before work starts, or an installer registered with a competent person scheme for the work self-certifies it and a compliance certificate follows.
How often should an unvented cylinder be serviced?
Approved Document G sets no interval, so follow the manufacturer’s instructions for your cylinder. One manufacturer’s manual recommends a maximum of 12 months between services, done by a competent person qualified to work on unvented cylinders.
Why is water coming out of the tundish?
The tundish shows when a safety valve is discharging. One manufacturer’s manual treats water flowing through it as a fault that needs a visit from a competent installer, and says not to turn off the cold water to the cylinder while the discharge is hot. The warning label in Approved Document G says to switch the heater off and contact the installer.