A guide for homeowners, landlords and gas engineers.
Expansion vessel: what it does on a boiler
An expansion vessel absorbs the pressure rise as a boiler heats the water in a sealed heating system, replacing the loft header tank of older systems. In both manufacturers’ manuals it is built into the boiler. One manufacturer says a rise of more than 1 bar when hot may mean it needs repressurising, which requires a service engineer.
Last updated
What does an expansion vessel do?
Water takes up more room as it heats and less as it cools. In a sealed heating system, the kind a combi or system boiler runs, the expansion vessel is the part that takes up the difference.
One boiler manufacturer puts it this way. Older systems used a header tank in the loft. A sealed system uses an expansion vessel instead, and the vessel absorbs the pressure rise when the boiler heats the system water.
In both boiler manufacturers’ manuals, the vessel is built into the appliance. One lists a 6 litre vessel as part of the appliance, with a Schrader type valve on it so the charge can be adjusted. The charge set at that valve is called the pre-charge pressure.
This page is a summary of manufacturers’ manuals and official guidance. Figures differ between appliances. The engineer must follow the current instructions for the appliance in front of them and remains responsible for the work. ClearWorks is not affiliated with Gas Safe Register or with the manufacturers listed in the sources.
Signs of a low charge or a failed vessel
These are the signs the manufacturers themselves give. Each one is a reason for a check. None of them proves the fault.
- The gauge climbs a long way when the heating is hot. One manufacturer says that if pressure rises by more than 1 bar once the heating is up to temperature, the expansion vessel may need repressurising.
- Pressure goes over 2.5 bar with the boiler running. One fault finding chart sends the engineer to the vessel at this point. It asks whether the pre-charge is higher than expected or too low. If it is too low, the vessel is repressurised. If not, the chart says to check that the vessel is correctly sized for the system.
- Water keeps needing to be added. The same manual’s service section says that when water is often needed to hold the pressure, and no leak has been found, an expansion vessel check is carried out.
- Water at the vessel valve. The second manufacturer’s manual says that if water escapes from the valve of the expansion vessel, the vessel must be replaced.
The first manual also says that where a system does not hold its pressure, the pressure relief valve and the heating system should be checked for leaks. For what the gauge should read day to day, see the boiler pressure guide.
Pre-charge pressure: two manuals side by side
| Point | First manufacturer | Second manufacturer |
|---|---|---|
| Pre-charge figure | 0.75 bar as supplied, which the manual equates to a static head of 7.5 m | Topped up if it measures under 0.75 bar |
| Matched to | Static head, at 1 metre = 0.1 bar, measured from the vessel to the top of the highest radiator | The static height of the heating installation |
| State of the boiler for the check | Depressurised, in an older manual from this manufacturer | Drained, with the reading taken at the vessel valve |
| How it is adjusted | At the Schrader type valve fitted to the vessel | Topped up with nitrogen ideally, otherwise air, with the drain valve open |
| When it is checked | When water often has to be added and no leak is found. The older manual says yearly | Listed in the maintenance table as “at regular intervals” |
| Filling the system | Set 0.1 to 0.25 bar above the vessel pre-charge | Heating system filled and purged again after the check |
Both manufacturers’ instructions take the water pressure off the boiler before the reading. The first manual’s sizing chart starts at a minimum pre-charge of 0.5 bar and runs up to 1.3 bar, which is why the figure on one job is not the figure on the next.
Who checks and recharges it
This is a service task for a competent engineer. The manufacturers say so in three places:
- The help page. One manufacturer says repressurising the expansion vessel will require a service engineer.
- The first manual. Alterations, servicing and repairs must only be carried out by a competent, registered gas engineer, such as a Gas Safe registered engineer.
- The second manual. Inspection and maintenance must only be carried out by competent persons who are sufficiently qualified.
For a householder, the useful step is to note what the gauge reads cold and hot, and tell the engineer. The vessel check then sits alongside the other items on the boiler service checklist.
Sizing: when a second vessel is needed
Both manuals tell the installer to check the built-in vessel against the size of the system.
- The trigger in one manual. An additional vessel must be fitted where the system volume is more than 100 litres, or where pressure exceeds 2.5 bar at maximum heating temperature.
- The method in that manual. A chart, not a formula. The installer works out the total system volume in litres and the maximum flow temperature, picks the curve for the pre-charge pressure, and reads off whether the built-in vessel has the capacity.
- Where it goes. Both manuals put the extra vessel in the heating return, as close to the boiler as possible.
- Its charge. One manual says to pressurise the extra vessel to the same value as the built-in one.
The chart to use is the one in the manual for the appliance being fitted.
Expansion vessels on hot water cylinders
An unvented hot water cylinder has its own vessel, on the hot water side. It is a separate part from the one in the boiler. Approved Document G defines it as a vessel that temporarily accommodates the expansion of water from the unvented hot water storage vessel as it is heated.
One cylinder manufacturer’s manual shows how the two differ in practice:
- It is a potable vessel. The manual calls the ones supplied with its cylinders potable expansion vessels. It recommends fitting them upright, with short connecting pipework, to prevent water stagnating.
- The charge is higher. 3 bar on the air side for that range, against the 0.75 bar figure in the boiler manuals above.
- The sign is at the tundish. The manual says a cold, intermittent discharge indicates a problem with the expansion vessel, and tells the householder to call the registered installer or a suitably qualified, competent tradesperson.
- Long pipe runs add volume. Where heated pipework holds more than 10 litres, the manual says an additional expansion vessel must be fitted.
A combi boiler can have a small vessel on the mains side too. One boiler manual says that where the mains supply has a non-return valve, a mini expansion vessel should be connected between that valve and the appliance. For the cylinder’s other safety devices and who may work on them, see unvented cylinders.
For gas engineers: record the vessel work
ClearWorks is a gas certificate app for Gas Safe registered engineers. The annual service goes on the service record. A call-out for pressure that will not hold goes on the breakdown record, which sets out the faults found and the work done. It works with no signal, so the record can be filled in beside the boiler.
The Gas plan is £15 per engineer a month plus VAT. Pay as you go is £2.50 a certificate plus VAT. Your first 3 certificates are free. See the gas certificate app and pricing.
Sources: Vaillant, Why is my boiler losing pressure?. Vaillant, ecoFIT pure installation and maintenance instructions (0020230531_07). Worcester Bosch, How often should I need to top up the pressure in the heating system?. Worcester Bosch, Greenstar 4000 installation and maintenance instructions (6 720 891 161, 2021/10). Worcester Bosch, Greenstar 24/28/30 installation, commissioning and servicing instructions (6 720 811 922, 2014/07). HM Government, Approved Document G (2015 edition with 2024 amendments). Gledhill, StainlessLite Plus design, installation and servicing manual (Iss07, 02/21). Last checked 18 November 2026.
Expansion vessel questions
What does an expansion vessel do on a boiler?
It takes up the extra volume when the heating water gets hot. One manufacturer says a sealed system uses an expansion vessel instead of a header tank in the loft, and that the vessel absorbs the pressure rise as the boiler heats the water.
What pressure should a boiler expansion vessel be?
It depends on the appliance and the height of the system. One manufacturer’s manual gives 0.75 bar as supplied. A second tops the vessel up if it measures under 0.75 bar. Both match the charge to the static height of the heating system.
How do I know if the expansion vessel has lost its charge?
One manufacturer says a rise of more than 1 bar when the heating is up to temperature means the vessel may need repressurising. Its manual also calls for a vessel check when water often has to be added and no leak has been found.
Can I recharge an expansion vessel myself?
The manufacturers treat it as a job for an engineer. One says repressurising the vessel will require a service engineer. Another says inspection and maintenance must only be carried out by competent persons who are sufficiently qualified.
Is the vessel on a hot water cylinder the same as the one in a boiler?
No. Approved Document G defines the cylinder’s vessel as one that takes up the expansion of water from the unvented hot water storage vessel. One cylinder manual calls it a potable expansion vessel and gives a 3 bar charge.