Guide for electricians, landlords and responsible persons
Fire alarm certificate: who needs one and when
A fire alarm certificate is not one form. It is a set of BS 5839 certificates for design, installation, commissioning, handover and servicing. This guide sets out what each one is, what the law in England requires, and where landlords stand.
Last updated
What a fire alarm certificate is
There is no single document called a fire alarm certificate. The phrase covers a set of certificates under two parts of BS 5839.
- BS 5839-1:2025 covers non-domestic premises. BSI lists it as current, published 30 April 2025, replacing the 2017 edition.
- BS 5839-6:2019+A1:2020 covers domestic premises. BSI lists it as current, published 31 October 2020.
Both are codes of practice. BSI says Part 1 is not itself a requirement to install a system in any building. The legal duties come from elsewhere.
For a Part 1 system, the Fire Industry Association (FIA) lists these documents for the responsible person to hold:
- Design certificate. States the category of system and any agreed variations.
- Installation certificate. Comes with as-fitted drawings.
- Commissioning certificate. Comes with the equipment manuals and user instructions.
- Acceptance certificate. Confirms the date of handover. The IET notes the 2025 edition now calls this stage “handover”.
- Inspection and servicing certificate. Issued after each service visit. This is what most people mean by a fire alarm test certificate or servicing certificate.
- Modification certificate (the 2025 edition calls it an extension or modification certificate). Records work done on the system after handover.
For dwellings, Approved Document B says a design, installation and commissioning certificate should be provided for the system.
This page is a summary. It is not the standard and it is not legal advice. Follow the current part of BS 5839, the manufacturer’s instructions and the fire risk assessment for the premises. You remain responsible for the work and for what you certify. ClearWorks is not affiliated with or endorsed by BSI, BAFE, the FIA or the IET.
Who needs one: legal duty and good practice
Non-domestic premises
The Regulatory Reform (Fire Safety) Order 2005 puts the duties on the responsible person. They must make a suitable and sufficient fire risk assessment (article 9). Where necessary, they must fit appropriate fire detectors and alarms (article 13) and keep them under a suitable system of maintenance, in efficient working order and good repair (article 17).
Articles 13 and 17 do not name a certificate or a British Standard. The certificates are how you show the duty has been met. The FIA says to keep them available for enforcing authorities and insurers.
Blocks of flats and HMO common parts
The Order does not apply inside a private home. Where a building contains two or more homes, it does apply to the common parts (article 6), so a system in the shared areas falls under the same duties.
Licensed HMOs
In England, every HMO licence must require a smoke alarm on each storey with living accommodation and a carbon monoxide alarm in any room used as living accommodation that contains a fixed combustion appliance other than a gas cooker. The licence holder must keep the alarms in proper working order and, on demand, give the council a declaration of their condition and positioning (Housing Act 2004, Schedule 4). The council can add its own conditions under section 67. Read your licence: that is where a requirement to produce servicing certificates would sit.
Licensed or not, the manager of an HMO in England must keep fire alarms in good working order (Management of Houses in Multiple Occupation (England) Regulations 2006, regulation 4). Separate 2007 regulations set the same duty for converted blocks of flats that count as HMOs under section 257 of the Housing Act 2004.
Single-let rented homes
The law sets a minimum for alarms, covered next. It does not ask for a certificate.
Landlords: the legal minimum in England
The Smoke and Carbon Monoxide Alarm (England) Regulations 2015, as amended in 2022, require a relevant landlord to make sure that:
- a smoke alarm is fitted on each storey that has a room used as living accommodation;
- a carbon monoxide alarm is fitted in any room used as living accommodation that contains a fixed combustion appliance, other than a gas cooker;
- each alarm is checked and in proper working order on the day a new tenancy begins;
- an alarm reported as faulty by the tenant is repaired or replaced as soon as reasonably practicable.
HMOs that need a licence, and houses that need a selective licence, are outside these Regulations because the licence conditions impose similar duties. HMOs that do not need a licence are covered.
None of this is a certificate requirement, and the Regulations do not say what type of alarm to fit. Government guidance recommends alarms that comply with BS 5839-6 and says the landlord should keep a record of the start-of-tenancy test, for example a line on the inventory that the tenant signs. The council enforces the Regulations by serving a remedial notice. A landlord who does not comply with it can be charged a penalty of up to £5,000.
England only. For Scotland, Wales and Northern Ireland, see smoke alarm regulations by nation.
Grades and categories at a glance
The grade describes the equipment. The category describes how much of the building is covered.
| Term | In plain words |
|---|---|
| Grade A | Separate detectors and sounders wired to central control and indicating equipment, with a back-up supply. |
| Grade C | Mains-powered detectors and sounders with a back-up supply and central control equipment. |
| Grade D1 | Mains-powered alarms, each with a tamper-proof standby battery. |
| Grade D2 | Mains-powered alarms, each with a user-replaceable standby battery. |
| Grade F1 | Battery-powered alarms with a tamper-proof battery. |
| Grade F2 | Battery-powered alarms with a user-replaceable battery. |
| LD1 | Escape routes plus every room where a fire might start. |
| LD2 | Escape routes plus the higher-risk rooms. |
| LD3 | Escape routes only: halls and landings. |
Grades B and E were removed from the current edition. A Grade D system is now either D1 or D2.
Approved Document B sets the minimum for a new dwelling in England at Grade D2, Category LD3. For existing rented housing, the LACORS housing fire safety guide gives examples for normal-risk property: Grade D with LD3 coverage for a single household of up to four storeys, and Grade D, LD3 plus interlinked detection in the kitchen, lounge and any cellar containing a risk for a shared-house HMO of up to four storeys. It does not recommend Grade F in HMOs. The guide dates from 2008 and uses the older grade names, so check it against the current standard and your council’s guidance.
Non-domestic systems use different letters. Approved Document B summarises them as Category M for manual systems, L for protection of life and P for protection of property. L1 and P1 cover the whole building. L2 to L5 and P2 cover defined parts or a specific objective.
Testing and servicing: what, how often, who
| Test | How often | Who | Record |
|---|---|---|---|
| User test (BS 5839-1 system) | Weekly, using a different manual call point each time | Premises management or someone they appoint | Logbook, including the call point used |
| Inspection and servicing (BS 5839-1 system) | About every 6 months. The 2025 edition accepts a visit 5 to 7 months after the last one | A competent person, usually a fire alarm servicing company | Inspection and servicing certificate, plus logbook |
| Grade D alarms in an HMO | Monthly, using the test button. Clean as the manufacturer says | Manager, or tenants given clear instructions | Faults reported to the landlord |
| Alarms in a rented home | On the day each new tenancy begins | The landlord, or someone on their behalf | The landlord’s own record, such as a signed inventory |
The first two rows follow FIA guidance on BS 5839-1 and the GOV.UK fire risk assessment guides. The 2017 edition said the gap between service visits should not exceed six months. The HMO row follows the LACORS guide, which predates the current BS 5839-6 and treats a Grade A system like a Part 1 system: weekly test, six-monthly service, certificate issued. BSI says the current edition has its own table of testing and servicing by grade, so work from that. The last row is the statutory check under the 2015 Regulations.
BAFE runs third-party certification schemes for firms doing this work: SP203-1 for non-domestic systems and DS301 for Grade D domestic systems.
How it relates to an EICR
They are separate documents under separate standards. An EICR reports on the fixed electrical installation against BS 7671. It does not certify the fire alarm system to BS 5839.
The two meet at the supply. BAFE notes that fire alarm installation work is done to BS 7671 for electrical safety. A new circuit for a panel or alarms is certified in the usual way: see the Electrical Installation Certificate guide. Emergency lighting has its own paperwork: see the emergency lighting certificate guide.
Your other certificates
If you do fire alarm work, you may also do EICRs and minor works in the same buildings. ClearWorks is a gas and electrical certificate app: gas safety records, the EICR, the EIC and the minor works certificate.
Sources: Regulatory Reform (Fire Safety) Order 2005, article 6, article 9, article 13 and article 17. Smoke and Carbon Monoxide Alarm (England) Regulations 2015, regulation 4, regulation 2 and regulation 8 (as amended). GOV.UK, smoke and carbon monoxide alarm guidance for landlords and tenants. Housing Act 2004, Schedule 4 and section 67. Management of Houses in Multiple Occupation (England) Regulations 2006, regulation 4 and the 2007 additional provisions regulations, regulation 5. BSI Knowledge, BS 5839-1:2025 and BS 5839-6:2019+A1:2020 (status and dates). FIA, Guide to the changes in BS 5839-1:2025, FIA technical bulletin on user responsibilities and FIA guidance for responsible persons (certificates, weekly test, servicing interval). IET Wiring Matters, key changes to BS 5839-1:2025. BAFE, SP203-1 and DS301. Approved Document B, volumes 1 and 2 (Grade D2 LD3 minimum, certificates, categories L, M and P). LACORS, Housing – Fire Safety (2008) (HMO grades, coverage and testing). GOV.UK fire safety risk assessment guides for offices and shops and sleeping accommodation. Grade wording corroborated by SELECT and Aico summaries of BS 5839-6.
Last checked 18 November 2026. BS 5839 is published by BSI and is not reproduced here. ClearWorks is not affiliated with or endorsed by BSI, BAFE, the FIA, the IET or LACORS. This guide focuses on England and is not legal advice.
Questions about fire alarm certificates
Do landlords need a fire alarm certificate?
For a single-let home in England, the law does not ask for a certificate. The Smoke and Carbon Monoxide Alarm (England) Regulations 2015 require a smoke alarm on each storey with living accommodation, a carbon monoxide alarm in any room with a fixed combustion appliance other than a gas cooker, and a check that they work on the day a new tenancy begins. Keep your own record of that check. HMOs are different: the licence may carry extra conditions, and the common parts fall under the Fire Safety Order.
What is a fire alarm test certificate?
It usually means the inspection and servicing certificate that a competent person issues after a service visit to a BS 5839-1 system. It is separate from the design, installation, commissioning and acceptance certificates issued when the system was new.
How often should a fire alarm be serviced?
For a non-domestic system, FIA guidance on BS 5839-1:2025 says inspection and servicing visits should be about six months apart, with a visit between five and seven months after the last one being acceptable. The user should also test the system weekly and record it in the logbook.
What is a Grade D fire alarm?
It is a system of mains-powered smoke or heat alarms with a standby battery in each alarm and no control panel. The current BS 5839-6 splits it into Grade D1, with a tamper-proof standby battery, and Grade D2, with a user-replaceable one.
Related pages