RCBO vs RCD: what is in your consumer unit

A circuit-breaker acts on overcurrent. An RCD acts on current leaking to earth. An RCBO does both in one device, usually for one circuit. That is why an earth fault on an RCBO consumer unit normally takes out only the circuit concerned, while a split-load RCD board can lose a whole bank.

Last updated

MCB, RCD and RCBO: what each one does

The three devices look alike in a consumer unit, but they watch for different things.

What each device responds to, as described by the IET and Electrical Safety First
DeviceResponds toRated inCovers
Circuit-breaker (MCB)Overcurrent and short circuit. It is the modern equivalent of a fuseAmps (A)One final circuit
RCD (the RCCB kind)Current leaking to earth. It has no overcurrent protection of its ownMilliamps (mA) for tripping, plus a current-carrying rating in ampsUsually a group of circuits
RCBOBoth. It is a residual current device with overcurrent protection built inAmps and milliampsUsually one circuit

An RCD compares the current in the live conductors of a circuit. In a healthy circuit they balance. When current leaks to earth the balance is lost and the device cuts the supply. The IET describes RCDs as far more sensitive than circuit-breakers.

“RCD” is also the family name. The IET lists the RCCB and the RCBO among its members. Electrical Safety First confirms that where BS 7671 calls for additional protection by RCD, an RCBO counts.

For how these devices are drawn on a plan, see our electrical symbols guide.

Split-load RCD board or consumer unit with RCBOs

Both layouts start with a main switch. The difference is where the earth leakage protection sits.

  • RCD consumer unit, split load. The IET’s guidance for householders calls this the usual arrangement: two RCDs, each protecting a number of circuits, with a circuit-breaker for each circuit.
  • RCBO consumer unit. A main switch, then an RCBO on each individual circuit. Electrical Safety First’s guidance for electricians describes this as the most common suggestion for meeting the Regulations.

Electrical Safety First says the two-RCD layout complies, as long as the circuits are shared between the RCDs with care so that the consequences of unwanted tripping are kept small. It adds that a single “front end” RCD should not protect every circuit.

An IET Wiring Matters article from November 2022 goes a step further. It says regulation 531.3.2 requires RCBOs to be considered, rather than grouped circuits on one RCD, in residential buildings. The stated aim is to reduce unwanted tripping and inconvenience. The article says considered, not fitted in every case.

The same article gives one reason grouping matters. Electronic equipment passes a small current to earth in normal use, which the article calls protective conductor current. It says the regulation requires that the total of these currents downstream of an RCD or RCBO should not exceed 30% of the device’s rated residual operating current. Circuits grouped behind one RCD add theirs together. An RCBO sees only the protective conductor current of its own circuit.

When a fault trips: one circuit or a bank

This is the difference a householder notices.

  • On a split-load board, an earth leakage fault on one circuit opens the RCD that feeds it. Every circuit grouped on that RCD goes off together. The IET’s example is upstairs and downstairs lighting placed on different RCDs, so that one tripping does not leave the whole home dark.
  • On an RCBO board, each circuit has its own device, so the leakage protection that operates is the one on the circuit concerned.

Whichever device trips, the IET says the likely cause is an appliance connected to the installation, not the installation itself. Electrical Safety First says an RCD that keeps tripping points to a fault that needs investigating, in an appliance or in the wiring. That is a job for a registered electrician.

Where BS 7671 asks for a 30 mA RCD

The IET’s model condition report for BS 7671:2018+A4:2026 has an inspection item for additional protection by an RCD not exceeding 30 mA. It lists:

  • all socket-outlets rated up to 32 A, unless an exception is permitted (411.3.3)
  • the supply of mobile equipment rated up to 32 A for use outdoors (411.3.3)
  • cables concealed in walls at a depth of less than 50 mm (522.6.202)
  • cables concealed in walls or partitions containing metal parts, whatever the depth
  • final circuits supplying luminaires in domestic (household) premises (411.3.4)

The same form has a separate item for all low voltage circuits of a location containing a bath or shower (701.411.3.3). The IET’s householder guidance sums it up: generally, every circuit in a home now needs this protection.

That describes work done today. Electrical Safety First says an older unit with no RCD is not necessarily unsafe, and that an EICR will tell you. To see what changed in the report itself, read BS 7671 Amendment 4 and the EICR.

RCD types: AC, A, F and B

An RCD or RCBO also has a type, which says what shape of leakage current it can detect. The IET’s Wiring Matters article “Which RCD type?” (September 2019) sets them out. Regulation 531.3.3 requires the type to suit the connected equipment.

RCD types as described in IET Wiring Matters, September 2019
TypeDetectsExamples the IET gives
ACAlternating sinusoidal residual current onlyEquipment without electronic components, such as an immersion heater or tungsten lighting
AAs AC, plus pulsating direct currentLED drivers and dimmers, induction hobs, IT equipment
FAs A, for frequency-controlled equipmentWashing machines, dishwashers, some air conditioning controllers
BAs F, plus smooth direct currentPhotovoltaic systems, some electric vehicle charging equipment

The IET’s FAQ explains the risk: direct current from electronic equipment can “blind” a Type AC device and stop it operating.

One trap from the same article: the RCD type is not the breaker curve. Circuit-breakers also come in types B, C and D, which describe their time and current characteristic. An RCBO with a B curve is easily mistaken for a Type B RCD.

Testing an RCD or RCBO

At home. Press the button marked “T” or “Test”. The device should switch off, and you then switch it back on. The IET says to do this every six months. Its FAQ notes that older labels say quarterly. If the device does not switch off, the IET’s advice is to consult a registered electrical contractor.

On an inspection. The schedule of test results on the BS 7671:2018+A4:2026 model forms has a column for RCD disconnection time and one for test button operation. A note on the form says RCD effectiveness is verified with an alternating current test at the rated residual operating current. Our guide to EICR testing covers the full sequence.

If a report recommends a new board, see consumer unit replacement for published costs and the notification rules. It is not a DIY job.

For electricians: record it on the report

ClearWorks is a certificate app for electricians. Fill in the EICR on your phone, one circuit at a time, to BS 7671:2018+A4:2026 and coded C1 to FI. Zs is checked against the protective device as you type, and readings outside limits are flagged. It works with no signal and saves on the phone.

When the remedial work is done, raise a minor works certificate linked to the EICR findings it fixes.

The electrical plan is £15 per engineer a month + VAT. Pay as you go is £2.50 a certificate + VAT. Your first 3 certificates are free.

EICR software for electricians

This page is a summary for general information, last checked 18 November 2026. It is not the standard and it is not design advice. Electricians must follow the current edition of BS 7671 and the manufacturer’s instructions, and remain responsible for the design, the work, the testing and the certificate. The IET Wiring Matters articles cited date from 2019 and 2022, so check the current wording of the regulations they quote. Householders should not open a consumer unit or carry out electrical work on it. ClearWorks is independent and is not affiliated with or endorsed by the IET, BSI, Electrical Safety First, NICEIC or NAPIT.

Sources: IET: consumer units guidance for consumers, consumer units and protective devices FAQs, BS 7671:2018+A4:2026 model forms; IET Wiring Matters: Which RCD type? (September 2019) and High protective conductor currents in electrical installations (November 2022); Electrical Safety First: Wiring Regulations help, your questions answered and advice for home buyers. Last checked 18 November 2026.

RCBO and RCD questions

What is an RCBO?

An RCBO is a residual current device with overcurrent protection built in. One device does the job of a circuit-breaker, which acts on overcurrent and short circuits, and of an RCD, which acts on current leaking to earth. In a consumer unit it usually protects a single circuit.

What is the difference between an RCBO and an RCD?

The kind of RCD that protects a group of circuits detects earth leakage only. The IET says it gives no overcurrent protection, so each circuit behind it still needs a circuit-breaker. An RCBO combines both functions. Electrical Safety First confirms that an RCBO counts where BS 7671 asks for additional protection by RCD.

Is a consumer unit with RCBOs required by BS 7671?

Electrical Safety First says separate RCD protection is not necessarily required for each circuit, and that a main switch with two RCDs can comply if the circuits are divided between them with care. An IET Wiring Matters article from 2022 says regulation 531.3.2 requires RCBOs to be considered in residential buildings to reduce unwanted tripping.

Why does the whole bank go off when my RCD trips?

On a split-load board one RCD feeds several circuits, so all of them lose power when it operates. The IET says the cause is more likely an appliance than the installation. If the device will not reset, or keeps tripping, contact a registered electrician.

How often should I test my RCD?

The IET says every six months, by pressing the button marked T or Test. The device should switch off and can then be switched back on. Labels on older installations say quarterly. If it does not switch off, seek advice from a registered electrician.

Which circuits need a 30 mA RCD?

The IET model condition report for BS 7671:2018+A4:2026 lists socket-outlets rated up to 32 A unless an exception is permitted, mobile equipment up to 32 A used outdoors, cables concealed in walls less than 50 mm deep or in partitions with metal parts, and circuits supplying luminaires in domestic premises. A separate item covers all low voltage circuits of a room containing a bath or shower.