For homeowners, landlords and electricians. England. Last checked 18 November 2026.

Electric shower installation: cost, rules and certificates

Published 2026 guides put electric shower installation at roughly £200 to £800 with the unit, less for a straight swap. It is an electrician’s job. Whether it is notifiable depends on whether a new circuit is needed. This page gives the prices by source, the rules in England and the paperwork to expect.

Last updated

Electric shower installation cost: published prices

The figures below are the named websites’ own, not ClearWorks’. Each row keeps the source’s VAT wording and page date.

Published prices for fitting an electric shower in the UK, as shown on 18 November 2026
SourcePriceWhat it coversVATPage date
HaMuch, supply and fit£320 typical. £200 to £800 overallThe shower unit and professional fitting. The range depends on the unit chosenNot statedUpdated 4 March 2026
HaMuch, labour£200 average. £80 to £160 to replace an existing electric showerLabour onlyNot statedAs above
HaMuch, London estimate£381Includes a shower valued at £115. Worked out from hourly and daily ratesExcludes VAT and call-out chargesAs above
Fantastic Services, fitting£200 to £600Fitting only. The guide says an electric shower needs a water feed and an electrical connection, and lists electrical work and a new water feed as usually charged separately. The unit is extra at £50 to £300Fitting: not stated. Unit price includes VATTitled 2026 UK price guide
Fantastic Services, fitting by regionRest of UK £150 to £300. London and the South East £180 to £360Fitting only. Electrical work may be charged within or on top of this“Figures include VAT”As above

Fantastic Services gives two fitting ranges on the same page: £200 to £600 in its text and £150 to £300 in its regional table. The page does not reconcile the two. Both guides say a straight swap costs less than a first-time fit. Fantastic Services says a new circuit run back to the consumer unit adds noticeably to the price. HaMuch says a replacement can take two to three hours, and a job that needs new wiring up to a day.

Prices change, so get a written quote that says whether the unit, the electrical work and the certificate are included. ClearWorks is not affiliated with any website or manufacturer named on this page.

Who should fit an electric shower

An electrician. Electrical Safety First says an electric shower must be installed by a registered competent electrician and be supplied on its own circuit. Two manufacturers’ UK installation manuals agree: fitting is for a qualified person, and the electrical work must comply with BS 7671 and the building regulations.

The reason is the load. Between them, the two manuals cover units rated from 7 kW to 10.8 kW. That is why a shower gets a circuit of its own and is not taken from a ring main, a spur, a lighting circuit or a cooker circuit, as one manual spells out.

Is fitting an electric shower notifiable?

In England, it depends on what the job involves. Regulation 12(6A) of the Building Regulations 2010 makes electrical work in a home notifiable when it is a new circuit, a replacement consumer unit, or an addition or alteration to an existing circuit in a special location. Our Part P guide covers the certification routes, so this page sticks to showers.

  • First-time fit. A shower where there was none needs its own circuit from the consumer unit. A new circuit is notifiable wherever it runs.
  • Like-for-like replacement. Approved Document P says replacements, repairs and maintenance are not notifiable anywhere. Its cooker example makes the same point: fitting the appliance is not notifiable unless a new circuit is needed.
  • A swap that changes the circuit. An electric shower sits inside the special location. Regulation 12(9) draws that space around the shower head: up to 2.25 m above the finished floor, or to the shower head if that is fixed higher, and 0.6 m out from the edge of the bath or tray. With no bath or tray, it is 1.2 m out from the centre of the shower head. An alteration to the existing circuit inside that space is notifiable.

Which case applies depends on what the electrician finds. Work that is not notifiable is still within Part P and still has to be safe. This page covers England.

What the electrician checks before fitting a higher-kW shower

A more powerful unit draws more current, so the existing circuit may not suit it. These points come from the two manufacturers’ manuals and the IET model condition report. They describe what an electrician assesses. They are not fitting instructions.

  • Protective device. One manual’s table runs from a 30/32 A circuit-breaker for a 7.0 kW unit to 45 A for 10.5 kW. The other recommends 45 A for its 9.8 kW and 10.8 kW models.
  • Cable size. The cable must carry at least the rating of the device protecting it. What a cable can carry depends on how it is run. One manual lists the same 6 mm² cable at 32 A in an insulated wall and 46 A clipped direct, and says the rating falls further where cable is bunched or insulated. For that reason it strongly recommends at least 10 mm² cable in most installations. It says a competent electrician must assess the site to decide the cable size and the permitted circuit length.
  • 30 mA RCD. Both manufacturers’ manuals call for a 30 mA RCD on the shower circuit. One requires it for new installations and recommends it when replacing a shower. The IET’s Amendment 4 model condition report has an inspection item for it: additional protection by an RCD not exceeding 30 mA for all low voltage circuits of a location containing a bath or shower (701.411.3.3). See RCBO vs RCD for the devices that provide it.
  • The supply and the consumer unit. One manual says that if the main supply fuse is rated below 80 A, the local electricity supply company must be asked to confirm the supply is adequate. The other advises contacting the supply company for any shower above 9 kW. It adds that a consumer unit rated below 80 A, or with no spare way, may mean a new consumer unit.
  • Double-pole isolating switch. Both manuals require a means of local isolation: a double-pole switch with at least 3 mm contact separation in each pole. Both give 45 A as its rating. One says it can be a ceiling pull-cord switch, or a wall switch placed where the zones allow.
  • IP rating. Both units are rated IPX4. The IET model condition report has inspection items for whether the IP rating of equipment suits where it is installed (701.512.2) and whether current-using equipment suits its position in the room (701.55).
  • Earthing. Both manuals say the shower must be earthed.

The figures are those manufacturers’ own, for their own models. The manual supplied with the shower being fitted is the one that counts.

The certificates you should be given

The form follows the work. The notes on the IET’s BS 7671 model forms set it out:

  • New shower circuit. An Electrical Installation Certificate. Its notes say it is for an addition or alteration where one or more new circuits have been introduced. See our Electrical Installation Certificate guide.
  • Alteration with no new circuit. A minor works certificate. Its heading limits it to work that does not include a new circuit. Its notes say it may also be used when equipment is replaced, with accessories and luminaires as the examples.
  • Notifiable work. A Building Regulations compliance certificate as well. Approved Document P says a registered installer, or their registration body, must give the occupier a copy within 30 days of completion.

Keep them with the papers for the home.

For electricians: the minor works certificate on site

When a shower job is an alteration that adds no new circuit, the paperwork is a minor works certificate. In ClearWorks you issue it on your phone before you leave. Missing details and readings outside limits are flagged, and Zs is checked against the protective device. It works with no signal.

The electrical plan is £15 per engineer a month + VAT. Pay as you go is £2.50 a certificate + VAT. Your first 3 certificates are free.

EICR software for electricians

This page is a summary for general information, last checked 18 November 2026. It is not the standard, a manufacturer’s instruction or legal advice. Electricians must follow the current edition of BS 7671, the Building Regulations and the instructions supplied with the shower, and remain responsible for the work, the testing and the certificates. ClearWorks is independent and is not affiliated with or endorsed by the IET, BSI, NICEIC, NAPIT, Electrical Safety First or any manufacturer or website cited here.

Sources: HaMuch electric shower installation cost guide; Fantastic Services shower installation cost guide; Building Regulations 2010, regulation 12; GOV.UK, Approved Document P (paragraphs 2.5 to 2.8 and 3.4); IET, BS 7671:2018+A4:2026 model forms; Electrical Safety First, staying safe in your bathroom; manufacturers’ installation manuals: Kohler Mira, Mira Elite SE (July 2023) and Triton, Zenica electric shower (2021), copy hosted by Wickes. Last checked 18 November 2026.

Electric shower installation questions

How much does electric shower installation cost?

Two published 2026 guides give the range. HaMuch puts a typical supply and fit at £320, within £200 to £800 depending on the unit. Fantastic Services puts fitting alone at £200 to £600, with the unit extra at £50 to £300. These are their prices, not ClearWorks’.

Is replacing an electric shower like for like notifiable?

In England, Approved Document P says replacements, repairs and maintenance are not notifiable. A new circuit is notifiable, and so is an addition or alteration to an existing circuit in the special location around a bath or shower. The work must be safe either way.

Can I install an electric shower myself?

Electrical Safety First says an electric shower must be installed by a registered competent electrician and be supplied on its own circuit. Both manufacturers’ manuals cited here say installation is for a qualified person.

Can a higher-kW shower go on the existing cable?

Only an electrician can say, after assessing the circuit. A more powerful shower draws more current. The cable, the protective device, the isolating switch and the supply all have to suit the new unit, and the manufacturer’s manual sets its requirements.

Does an electric shower need an RCD?

Both manufacturers’ manuals call for a 30 mA RCD on the shower circuit. One requires it for new installations and recommends it when replacing a shower. The IET model condition report has an inspection item for 30 mA RCD protection of all low voltage circuits in a location containing a bath or shower.

What certificate should I get after an electric shower is fitted?

For a new circuit, an Electrical Installation Certificate. For an alteration that adds no new circuit, a minor works certificate. Where the work is notifiable in England and a registered installer does it, you should also receive a Building Regulations compliance certificate within 30 days.